Use of fire walls to “separate” buildings. While the code does not explicitly require fire walls, they may be utilized in many cases to expand the prescribed size of a building. (See Parkside sidebar.)

IBC Section 706 permits portions of a building separated by one or more fire walls to be considered as separate, side-by-side buildings. In this way, wood-frame buildings can be designed as separate but connected buildings for code-compliance purposes. This partitioning allows wood buildings to be unlimited in size.

Mezzanines. IBC Section 505 excludes mezzanines from the determination of number of stories or building area. Mezzanines may be one-third of the floor area of the room or space beneath. For example, a loft or penthouse plus a mezzanine on the first concrete podium floor could add two “stories” to the building.

Podium design. In multi-level wood-frame buildings, architects and engineers are increasingly turning to podium or pedestal design—which can add another floor level to the maximum permissible number of stories—instead of building directly on a concrete slab on grade. Section 510.2 of the 2012 IBC allows five- or six-story wood-frame structures over one level of typically concrete Type IA construction. These “five-over-one” and “six-over-one” buildings are treated in the code as two structures separated by a three-hour fire-resistance-rated horizontal assembly.

The podium is considered as a separate and distinct building for the purpose of determining height and area limitations and vertical continuity of fire walls. The overall height of the two buildings together is measured from grade plane, and the height limitations of Chapter 5 apply. The 2015 IBC will expand this opportunity by allowing two or more stories below the three-hour horizontal fire assembly with the caveat that the overall building height from grade still not exceed the limits set out in Chapter 5.

 