Site Lighting: Optical Systems Design and Application Guide for Site and Roadways
Selecting the right type of site lighting enhances building design, efficiency, and safety
Continuing Education
Use the following learning objectives to focus your study while reading this month’s Continuing Education article.
Learning Objectives - After reading this article, you will be able to:
- Identify the lighting requirements in each area of site lighting.
- Describe different methods to direct light toward intended areas or away from areas not to be illuminated.
- Describe lighting distribution types and how they are best suited for lighting outdoor environments.
- Explain how isofootcandle plots are used to design site lighting.
Architecture and light: The two are intertwined in good design of all buildings, but the same is true of building sites. Outdoor spaces frame and enhance any building design. Depending on the lighting used, these outdoor spaces can create settings that might be attractive or mysterious, inviting, or secluded, secure-feeling or foreboding. With buildings and spaces being used during more hours of the day and night, good site lighting design becomes as important as good building lighting design.
Outdoor lighting, like all artificial illumination, is based on an understanding of light principles and the specification of luminaires that meet one's objectives. A luminaire is defined by the Illuminating Engineering Society of North America (IESNA) as "a device to produce, control, and distribute light. (It is) a complete lighting unit consisting of the following components: one or more lamps, optical devices designed to distribute light, sockets to position and connect the lamps to a supply of electric power, and the mechanical components required to support or suspend the housing above grade."
From a pure lighting standpoint, the main items that differentiate luminaires are the internal optical system and the lamp (bulb) unit. The function of an optical system is to direct light energy emitted by the lamp into desirable areas. This function can be accomplished through reflection, diffusion, baffling, refraction, or transmission through a lens. Lamp placement within the luminaire also plays a significant role in determining optical system performance. Using the lamp's natural distribution pattern to its greatest advantage produces the most effective optical designs. For example, a horizontal lamp orientation produces asymmetric light distribution patterns, while vertical lamp orientation produces a strong symmetric pattern. Reflector and lens designs that enhance these characteristics produce the most efficient results.
|
IESNA also identifies performance and design considerations as follows, "Luminaire performance can be considered a combination of photometric, electrical, and mechanical performance. Photometric performance of a luminaire describes the efficiency and effectiveness with which it delivers the light produced by the lamp to the intended target." Luminaire manufacturers need to consider a wide variety of factors in designing and producing their products. Architects and other design professionals need to be aware of fundamental criteria in designing lighting layouts and specifying luminaries for use on their projects.
I. SITE LIGHTING AREAS AND DESIGN INTEGRATION
Any given building site usually has differing uses and conditions-each has differing lighting requirements as well. Therefore, meeting the diverse needs of site illumination requires a variety of different solutions that can be coordinated and integrated to complement the building design. Such an integrated site lighting design begins with first identifying the specific lighting requirements for each portion of the site, then selecting luminaires that combine appropriate aesthetic design with relevant lighting performance features.
Conceptually, project sites can be classified into four basic lighting areas; roadways, open areas, pedestrian areas, and the site perimeter, each representing a unique set of lighting circumstances, as described below and shown in Figure 1.
|
1. Roadways
Lighting for roadways, including private drive lanes, usually
requires uniform light distribution and glare control with
wide pole spacings to minimize the total number of luminaires
needed. Luminaire selection criteria include overall performance,
consideration of maintenance, lamp choices influenced by utility
or owner interests, and the ability to remain in service for
long periods with minimal attention. Reflectors and optical
designs within the luminaires include an array of possible
light distribution patterns in order to illuminate varied
roadway widths and traffic patterns with narrow perpendicular
and wide lateral beam spreads.
2. Open Areas
Lighting of open areas requires careful consideration of illumination
requirements, uniformity, and brightness control. These areas
are usually subject to scrutiny relevant to the safety and
security of site occupants and the interaction between vehicle
and pedestrian traffic. Parking areas and connecting walkways,
in particular, are a potential source of litigation and liability
for the project owner, requiring accurate prediction of illumination
levels and dependable performance. In order to optimize visibility
for all users, it is important to control illumination levels,
uniformity of light distribution, and glare. At the same time,
an economical layout will be based on maximizing the spacing
of luminaires.
3. Pedestrian Areas
The transition between the surrounding site and the building
itself defines the pedestrian area, including plazas, courtyards,
and pathways. These spaces require the widest range of lighting
solutions since they combine the concerns of open areas and
the integration of luminaire appearance with the building's
architectural design. Luminaires in this area are usually
highly visible, requiring attention to finish quality and
detail. Illumination of irregularly shaped spaces, and a need
to control stray light, requires optical diversity, particularly
since fixture placement may be influenced by aesthetic concerns.
Ideally, if the appearance and design components of the luminaires
specified in these areas are shared with other site luminaires,
the integration of the lighting system for the entire site
is enhanced.
4. Site Perimeter
Lighting the site perimeter includes requirements to control
or eliminate illumination from "trespassing" onto
adjacent properties. Light trespass ordinances, and courtesy
to neighboring property occupants, require tight control of
light emitted behind the luminaire. Efficient design satisfies
some of this demand, while optics inside the luminaire that
cut off light distribution in certain areas provide an additional
level of control. House-side shields may also be required
to provide even tighter control by trimming the distribution
pattern. These concerns must be satisfied, of course, without
affecting overall system performance.
II. PHOTOMETRY INFORMATION
The design of site lighting requires an understanding of the unique information used to represent elements of optical performance. Photometry, or the measurement of light intensity and relative illuminating power, is the foundation on which any evaluation of luminaire performance is based. Use of independent testing labs to conduct the measurements and compile the information ensures that the photometry information is accurate and reliable.
Basic Language and Presentation
In order to properly select luminaires appropriate to the
specific locations and requirements of a building site, an
understanding of some of the basic language and ways that
information is presented is required.
|
Candela Tabulation
One of the fundamental units of measurement is the candela,
which in 1979 became the international standard to define
luminous intensity. Figure 2 shows a typical candela tabulation
data sheet prepared by an independent lab with a luminaire
orientation diagram for reference.
The Candela Tabulation Data Sheet presents the raw data used for all illuminance calculations and is tabulated with the vertical angles in rows and lateral angles in columns. As the diagram indicates, lateral values from 0° to 90° are in front of the luminaire and referenced as "Street Side." Lateral values from 90° to 180° are behind the luminaire and referenced as "House Side."
Vertical values from 0° to 90° are below the fixture, while values 90° to 180° are at the fixture level and above. As we will see, candela data is also used to define a luminaire's light distribution type and cutoff characteristics.
Footcandle Calculations
The data provided in Candela Tabulation Data Sheets is used
to calculate footcandle levels within a proposed lighting
design. Generally, this is accomplished by using computers
to make calculations, which are, in turn, dependent upon the
accuracy of the data. Figure 3 illustrates the relationship
of the calculated illumination at a single point to the information
provided in the candela tabulation. (See Figure 7 later in
this article for the correlating location on an isofootcandle
plot.)
|
Candela Plots
Candela plots are graphical representations of candela tabulation
data (figure 2). Outdoor lighting produces unique light patterns
which are difficult to represent in a flat two-dimensional
plane. Therefore, to create distribution plots that illustrate
luminaire performance, curves are plotted with a three-dimensional
dynamic. An example, based on the candela tabulation data
above, is presented in the charts shown in Figure 4.
Using the tabulated maximum candela value, which in this example is 8595, two planes are identified: a lateral angle of 71°, and a vertical angle of 66°. The vertical angle is used to create a cone, with its slope equal to the vertical angle of maximum candela (66°). On this cone, all lateral candela distribution values from the tabulated data row at 66° are plotted. The result is shown on the right side of the cone chart. The two-dimensional view looks down at the top of the constructed cone.
|
The second value, the lateral angle of 71°, is used to construct a vertical plane off the lateral baseline. The result is shown on the left side of the cone chart. On this surface, all vertical candela distribution values from the tabulated data column at 71° are plotted. For purposes of presenting the plot, the vertical plane is flattened, or laid back 90°, to show it in the same plane as the right side plot.
The chart is also shown in a perspective view, to help visualize the relationship between the two plotted curves. The combination of the two curves represents luminaire performance in three dimensions.
III. LIGHT DISTRIBUTION PATTERNS
Outdoor luminaires produce lighting patterns that can be identified first by their reach in front of a single fixture location and second by their reach on each side of that location. "Distribution types" describe the reach of the luminaire's light pattern forward of each fixture, while "distribution ranges" define the reach to either side.
|
Distribution Types
(Refer online for example illustrations of each Distribution
Type).
The term "distribution type" defines how far forward
of the luminaire (i.e., on the street side) the effective
output reaches. The specific classification of distribution
types is based on locating the luminaire's effective
major output pattern on a grid representing distances in units
of Mounting Height (MH) from the luminaire. This pattern is
defined by tracing an area representing light distribution
at 50% of maximum candela. By measuring where the bulk of
this pattern falls on the grid, a luminaire can be classified
as follows and as shown in Figure 5. Refer to illustrations
of definitions online. (Note that in some cases, minor deviations
in a beam pattern may cross the boundary from one type into
another. While this has a nominal effect on applied performance,
it should not be considered for classification purposes.1):
- Type II defines shallow reaches, when the 50% maximum candela trace lies within1.75 MH on the street side of the reference line.4
- Type III is a mid-range, when the 50% maximum candela trace lies within 2.75 MH on the street side of the reference line.4
- Type IV identifies luminaires with a definite forward-throw distribution, when the 50% maximum candela trace lies beyond 2.75 MH on the street side of the reference line.4
- Distribution is classified as Type V Square for horizontal
lamp luminaires when
the 50% maximum candela trace is symmetric in four quadrants. This distribution is characterized by four candela peaks, diagonal to the reference line. - Asymmetric5,6 Distribution (similar to Type III): This distribution is for vertical lamp luminaires when the 50% maximum candela trace lies beyond 1.0 MH on thestreet side of the reference line, and inside 1.0 MH on the house side of thereference line. Narrow range distribution is identified when the point of maximum candela falls inside of 2.25 MH; wide range is identified when the point of maximum candela falls beyond 2.25 MH.
- Symmetric5,6 Square Distribution (similar to Type V Square): Distribution is classified as symmetric square for vertical lamp luminaires when the 50% maximum candela trace is symmetric in four quadrants on both street and house side of the reference line. Narrow range distribution is identified when the candela peaks fall inside of 2.25 MH along the reference line; wide range is identified when the candela peaks fall beyond 2.25 MH.
Distribution Range
Distribution range defines how far the distribution pattern
reaches laterally, perpendicular to the axis used to identify
general type. The ranges used are defined as follows and indicated
graphically in Figure 5.
Long Range: A distribution is identified as long range when the point of maximum candela lies from 3.75 to 6.0 MH from the luminaire's centerline, along the reference line.
Medium Range: A distribution is identified as medium range when the point of maximum candela lies from 2.25 to 3.75 MH from the luminaire's centerline, along the reference line.
Short Range: A distribution is identified as short range when the point of maximum candela lies from 1.0 to 2.25 MH from the luminaire's centerline, along the reference line.
Very Short Range²: A distribution is identified as very short range when the point of maximum candela lies from 0 to 1.0 MH along the reference line.
Distribution types only generally describe a distribution pattern. To establish the suitability of a luminaire for a specific application, an evaluation must be completed using actual photometric data for the specific fixture and lamp combination being considered.
IV. CUTOFF
Beyond distribution and range, luminaires are defined by how well they control or cut off light at selected vertical angles. Typically this reference point is referred to as zero degrees vertical or "nadir". Designs without significant cutoff characteristics distribute light in zones unlikely to contribute to useful visibility, contribute to light pollution, and are inefficient.
|
Definitions
The definition of cutoff is based on what proportion of a
luminaire's output is being distributed at 80° and
90° above nadir. See figure 6 for graphic examples of
some of the luminaire cutoff types defined below. (Extracted
from IES Publication RP33-99 (2/99))
Noncutoff
A luminaire's light distribution is designated as noncutoff
when there is no limitation of illumination in any zone.
Full Cutoff
A luminaire's light distribution is designated as full
cutoff when the candela at 90° above nadir is 0 and less
than 10% of rated lamp lumens at 80° above nadir.
Cutoff
A luminaire's light distribution is designated as cutoff
when the candela at 90° above nadir is less than 2.5%
of rated lamp lumens, and less than 10% of rated lamp lumens
at 80° above nadir.
Semicutoff
A luminaire's light distribution is designated as semicutoff
when the candela at 90° above nadir is less than 5% of
rated lamp lumens, and less than 20% of rated lamp lumens
at 80° above nadir.
Example:
A luminaire with tested data showing a total of 16,000 Rated
Lamp Lumens has a candela tabulation that produces 18 candela
at 90° (<2.5% of Rated Lumens) and 55 candela at 80°
(<10% of Rated Lumens). These values fall within the defined
ranges shown in Figure 6, classifying this as a cutoff luminaire.
VI. ISOFOOTCANDLE PLOTS
Isofootcandle plots are a common tool for evaluating and comparing different luminaires for a given application. These plots are often provided by luminaire manufacturers for architects and engineers to use in selecting and specifying appropriate lighting products. An example is shown in Figure 7.
Usage
Isofootcandle plots graphically represent a particular luminaire's
lighting pattern, in illuminance, as the light strikes a horizontal
surface. These plots are scalable as they are represented
in mounting height increments. An approximation of pole spacings
required to attain a desired light level can easily be determined
from the information provided. These plots also provide a
productive tool for the comparison of various luminaires.
The easily read visual reference indicates beam patterns graphically,
where other information (such as candela tabulations and isocandela
curves) may be less clear.
Conventions
Isofootcandle plots include footcandle calculations shown
with the luminaire at various mounting heights. Contour lines
are drawn through illuminance values. Each contour, from the
center out, represents approximately 50% of the value of the
previous contour. The plot of contours is placed over a grid
indicating mounting height divisions to demonstrate the luminaire's
applied performance.
|
Estimated Spacing and Uniformity
As early as the schematic design phase of a project, isofootcandle
plots can be used for rough luminaire layouts for site lighting.
EXAMPLE: Refer to the isofootcandle plot in Figure 8 and assume a desired minimum initial illuminance of 2.0fc, using luminaires mounted on 14' poles. To estimate a fixture layout, start from the perimeter, where the 2.0fc isofootcandle trace crosses the reference line, to establish the maximum single fixture distance to the site perimeter (1.6 MH). In order to attain the minimum illuminance (2.0fc) between fixtures, the 1.0fc traces of two fixtures must intersect at the site perimeter and interior. Therefore, lateral spacing is determined where the 1.0fc trace intersects the reference line (2.2 MH), and maximum forward spacing is identified where the lateral spacing line intersects the 1.0fc trace on the street side of the luminaire (1.8 MH). These two dimensions indicate the mid-points between luminaires, in mounting heights. Multiplying these mounting height (MH) dimensions by the pole height (14') defines the maximum luminaire spacings in both directions. In this example, 60' (4.4 MH x 14') x 50.4' (3.6 MH x 14').
Approximate Illuminances and Uniformity
By overlaying isofootcandle plots, a rough idea of illuminances
can be determined by adding the values of each contour where
they intersect as shown in the lower portion of the example
in Figure 8. Through observation of the overlapping of the
isofootcandle plots, approximate uniformity can also be estimated.
More accurate calculations (computer generated evaluations)
will generally return levels higher than those achieved using
this method, as smaller contributions from every adjacent
luminaire would be included.
VII. APPLICATION IN DESIGN
Distribution Pattern Uses
Ideally, all light energy produced would be focused into desired
lighted zones with no wasted energy being directed elsewhere.
This would require an infinite array of distributions, and
the ability to tune them to every site condition. While this
is not realistic, the combination of careful luminaire selection,
mounting height, and luminaire placement can produce very
efficient designs, using just four basic distribution patterns,
as shown in Figure 9. For each of the basic distributions,
variations such as range and the characteristics of horizontal
vs. vertical lamp optics produce additional choices. Further
fine tuning can be attained with house-side shields and reflector
orientation.
|
The sample site plan in Figure 10 shows how the combination of these four basic distribution patterns are used to direct light energy into the lighted zones.
|
Important Features for Fine-Tuning Designs
Lamp Orientation: Horizontal lamp orientation provides the greatest control over lateral distribution. The normal lamp distribution is very well suited for asymmetric as well as square symmetric distribution. Horizontal lamp orientation produces relatively small arc tube exposure to high distribution angles. This produces a superior cutoff characteristic.
Vertical lamp orientation subjects the greatest portion of the lamp's output to control by the reflector system, producing optimal vertical distribution control. This orientation provides less control over lateral output, favoring symmetric distribution patterns. Vertical lamp orientation also takes advantage of the higher lumen output produced by a vertical arc tube positioning.
|
|
Square vs. Round Distribution: For large areas, symmetric distributions provide maximum pole spacing in both lateral and longitudinal directions. Round distributions, however, do not reach well diagonally between pole locations, reducing uniformity and requiring shorter distances between luminaires. Square distribution patterns are specifically engineered to maximize pole spacing by improving uniformity diagonally between fixture locations. As shown in Figure 11, a typical round pattern produces poor diagonal overlap, requiring tighter pole spacing to maintain acceptable uniformity. A Type V Square Pattern provides improved diagonal overlap allowing wider pole spacing while maintaining excellent uniformity.
House-Side Shields: When luminaires are located close to structures, or areas where the illumination emitted on the house-side of the reference line is objectionable, house-side shields offer additional cutoff control. These devices essentially trim light emitted by the lamp, as well as light reflected from within the optical system. These are applied to Type II, Type III and Type IV (horizontal lamp) and Asymmetric (vertical lamp) optical systems only as shown in Figure 12. House-side shields are not applied to Type V or Symmetric optical systems, as the shields will not function properly in these systems.
|
It should be noted that the effects of lamp orientation and lens configuration on house-side shields are dramatic. Main reflector distribution, street-side reflector brightness, and direct lamp visibility are factors that determine the effectiveness of house-side shields in reducing unwanted brightness on the house-side of the optical system. Horizontal lamp orientation presents the greatest challenge in designing effective shielding. Convex lenses allow more effective control, as the shielding device is able to better control direct arc tube brightness. Vertical lamp orientation provides even greater control, as the arc tube is already deeper in the optical system.
Reflector Orientation/Rotatable Optics
Orientation of luminaires is often controlled by available
pole locations and a product's aesthetic design. The luminaire's
head, arm, or yoke, however, may dictate an orientation that
varies from the desired optical orientation. The ability to
rotate optical systems provides a high degree of flexibility
to tailor luminaire performance to specific applications,
while maintaining the aesthetic continuity of the luminaires
used. The combination of optical distributions in multiple
luminaire applications produces additional unique "footprints,"
creating customized performance and/or increased illumination
levels to suit a very wide range of needs. Figure 13 shows
just a few examples based on a simple twin mounting arrangement.
|
Footnotes:
- ITL Reports using IES guidelines consider any crossing of the identified boundaries as definition of overall type, regardless of its impact or significance to applied performance. Classifications indicated do not consider minor deviations in classification of type shown.
- The "Very Short Range" identification is not an IES standard definition, but isused by ITL to identify distributions with ranges inside the 1.0 MH allowed in the "Short Range" definition established.
- Information shown is for illustrative purposes only and does not represent a specific luminaire's performance.
- Definition is extracted from IES Lighting Handbook, 8th edition.
- Definition has not been identified by the IES at this time. Definition shown is based on Kim Lighting research and development efforts and engineering of optical systems to improve applied performance.
- Distribution may be classified by ITL, using IES standard
practices, as a Type IV
distribution, due to a small portion of the 50% isocandela trace falling beyond the 2.75 MH line. This aberration in classification methodology conflicts with luminaire applied performance. Classification indicated more accurately represents actual luminaire usage.
|
CASE STUDY
The expansion and beautification of
the Minneapolis Community & Technical College (MCTC) parking
ramp.
Bentz/Thompson/Rietow (BTR), Architects-of-Record
The Minnesota State Colleges and Universities system (MnSCU) gained control of the MCTC and its associated power plant and parking ramp. However, the parking ramp, having had no true upgrades to its exterior and having had a less than urban-friendly original design, became known as a blight on the area, poorly representing the college and the site's importance. The original ramp, built in 1978 for the Minneapolis Public School system, was one of the first major public design/build projects. The original design, while inventive in the use of long-span precast concrete wall panels, did little to harmonize with its surroundings and little to respond to the importance of the site, which is truly a spectacular location. The ramp is located on the major public thoroughfare through downtown, Hennepin Avenue. This roadway has historically been one of the storied streets in the city; it is the gateway to the city from the west and crosses the Mississippi River to the east, and is known as the entertainment avenue for the city. After a decline in the area that lasted several decades, this downtown street has once again established itself as a major theater district with numerous eating establishments, clubs, bars, and plenty of nightlife.
Early on, the design team resolved that the project needed to reinforce the urban edge. The team also posited that the ramp should have a dynamic façade response that could change from night to day and could respond to differing light and climate conditions. In order to balance the need for an increased height/mass of the façades with the budget, the team began working with the concept of light structures that would provide a layering effect and serve as a theatrical scrim. The material had to be light yet strong, beautiful yet inexpensive, durable yet open enough to provide a safe environment for patrons. Heavily anodized, swaged aluminum floor grating was used because it met all of the design criteria. This material was used in a vertical application for the light columns that march down Hennepin Avenue. The same material was used in horizontal application to serve as the background scrim for the façades. Mullionless channel glass was used at the main stair towers to provide natural light into the stairs and to serve as urban-sized lanterns along the façade.
The design drastically improves the image of the structure during the day and, by using materials similar to ones used on the adjacent campus, finally makes the structure seem to be part of the same institution. The gentle curves at the cornice of the scrim and the bay spacing/proportions of the light columns recall heights, proportions, and details of an adjacent basilica. The ramp takes a background role to the basilica during the day. At night, the ramp takes on a special presence; it becomes a glowing, theatrical piece that calls attention to the campus and serves as a distinct gateway to city and the entertainment district.
|
Exterior lighting design was crucial to the success of the project. The team realized that lighting and material had to be synthesized in such a manner that would leverage the design intent without incurring large construction costs. Because the existing ramp had drastically different perimeter conditions in relationship to the scrim motif, the team needed fixtures that could be mounted in a variety of conditions while still having the same photometric distribution on the scrim. The result of this creative and collaborative design can be seen in Figure 14 (Photo credit Phillip Prouse).
According to Gary F. Milne Rojek, AIA Principal at BTR, "Designers need to understand what surfaces are going to be lit, what level of illumination is desirable, what amount of spread and control is required, and how to coordinate with other lighting on the project. On our ramp project, it was extremely important for us to illuminate the horizontally oriented grating in a very uniform and white light. The uplighting that was used had a very wide and uniform distribution that evenly illuminated the horizontal bars yielding the design intent of a theatrical scrim. The curvature of the grating at the top of the bands provides a subtle variation in reflectance. On the vertically oriented column grating, much narrower spread fixtures were used in order to emphasize the column elements in front of the scrim. Both of these design concepts had to be balanced with the distribution and color range of the standard ramp downlights."
The building owner has high praise for the results. Sally Grans, AIA, Director of Facilities Planning and Programming at MnSCU notes, "Other people need to see just how plain beautiful this once-ugly duckling parking ramp has now become a jewel! It is rare to see lighting as a work of art and this parking ramp is now truly artful. My only concern is that people don't get into car accidents as they slow down to look at it!"
Security Commentary
Security and site lighting often go hand in hand. There are
some specific details that can help to ensure increased levels
of security (and the perception of security).
Martha J. Droge, an Associate at Ayers/Saint/Gross in Baltimore, was a police officer before becoming a landscape architect. She writes and speaks often about site security and offers the following points:
- Metal halide lights render the vertical plane visible at a nearer distance than sodium lamps. This is important from a security perspective because the vertical plane is where the human face and hands are revealed as one approaches a person. Seeing the face and hands as soon as possible increases a pedestrian'ssense of safety and aids security personnel when patrolling an area.
- Depending on the technology, CCTV cameras and/or night vision aids can be thrown off by bright lighting. Obviously, the lighting plan and the security technology/perimeter surveillance plan should be well-coordinated.
- A lighting plan for a large complex of buildings or campus should designate certain routes as primary pedestrian routes after dark. Depending upon the circumstances, the primary routes might be the most direct paths between major spaces or parking lots, or the paths that keep pedestrians near safe, after-darkactivity areas (buildings with people coming and going, security patrols, positive night life activities, etc.). Primary paths should receive excellent comprehensivelighting and welcoming landscapes as cues to pedestrians to take those paths after dark. Secondary after-hours routes may have lighting for basic safety, but pedestrians should be directed to the primary routes after dark through coordination with campus maps and directions from campus representatives.
Keeping some of these points in mind when preparing an overall site lighting plan and layout can go a long way toward improved security conditions in outdoor settings.
About the article sponsor: Kim Lighting is known throughout the world as the premier designer and manufacturer of quality, high performance, architecturally relevant, outdoor lighting solutions. Kim has designed and manufactured outdoor lighting products for over seven decades and now occupies more than 400,000-square feet of factory space in the City of Industry, Ontario, and La Mirada, California employing over 600 people. Kim owes a great deal of its success to the core values established by its founder, F.B. Nightingale; innovate, educate, and never compromise quality. Kim Lighting, "The Ultimate in Architecturally Relevant Outdoor Lighting." Learn more atwww.kimlighting.com.